    COMMON SPECIFICATIONS FOR INFINITY METERS
    Accuracy
    : ±0.005% rdg
    Span Temperature Coefficient: ±20 ppm
    Step Response: 1 sec to 99.9%
    Warmup to Rated Accuracy: 50 min
    Operating Ambient: 0 to 50°C (32 to 122°F), 95%RH, non-condensing
    Storage Ambient: -40 to 85°C (-40 to 185°F)
    Power: 115 or 230 Vac, 49-400 Hz; 10 to 32 Vdc
    Power Consumption: 6 W nominal, 10 W max.
    Normal Mode Rejection: 60 dB
    Common Mode Rejection: 120 dB
    Common Mode Voltage: 1500 V peak per HV test
    Resolution: 15-bit
    Conversion: dual-slope technique
    Reading Rate: 3/sec or 13/sec, 60 Hz; 3/sec or 12/sec, 50 Hz
    Display: red or green 6-digit, 14-segment, 13.7 mm (0.54"); 4 alarm indicators
    Dimensions: 48 H x 96 W x 165 mm D (1.9" x 3.8" x 6")
    Panel Cutout: 45 H x 92 mm W (1.8" x 3.6"); 1/8 DIN
    Weight: 0.58 kg (1.3 lb.)
    TTL Outputs: four, isolated open collector; rated 150 mA at 1 V sink, 30 V open
    BCD Output: isolated, tri-state, TTL/CMOS compatible; external 5 V supply for isolated; internal 5 V supply for non-isolated
    Dual Relays: form C, 7 A at 30 Vdc or 230 Vac
    Four Relay Option: dual 7 A relays and dual 1 A relays
    Analogue Output: 0-5 V/1-5 V/0-10 V/0-20 mA/4-20 mA, user selectable; 354 Vp isolation; 15-bit resolution; 0.1% accuracy, 50 msec step response

    RS-232 Communications: 300/600/1200/2400/4800/9600/19.2k baud; RJ11 4-wire connection; complete program setup and message display capability; programmable to transmit current display, alarm status, min/max, actual measured input value and status

    RS-485 Communications: 300/600/1200/2400/4800/9600/19.2k baud; RJ12 6-wire connection; addressable from 0 to 199

10-Channel Unit
Rear View 10-Channel Units Feature Screw Terminal Connections; Single Channel Units Feature Standard Size Thermocouple Connector (Mating Connection Supplied).


PROCESS INPUTS—INFU, INFP, INFS, INFW
Voltage Input Ranges:
0-100 mV, 0-1 V, 0-5 V, 1-5 V, 0-10 V, 0-100 V, ±50 mV, ±500 mV, ±5 V, ±50 V
Current Input Ranges: 0-20 mA, 4-20 mA
Input Configuration: single-ended
Polarity: unipolar/bipolar, programmable
Span Adjustment: +0.00001 to 500,000, programmable
Offset Adjustment: 0 to 999,999 or 0 to -99,999; programmable

TEMPERATURE INPUTS—INFU, INFT
Thermocouple Input Types: J, K, T, E, R, S, B, N, J DIN
RTD Input: any 6 to 6k NIST or DIN platinum and any linear RTD
RTD Connection: 2-, 3- or 4-wire
Sensor Break Protection: upscale or downscale, programmable
Overvoltage Protection: 25 V peak

SENSOR EXCITATION—INFP, INFS, INFU, INFW
Sensor Excitation, INFS, INFU, INFW:
10 V at 30 mA; 24 V at 25 mA
Sensor Excitation, INFP: 24 V at 25 mA


INFINITY Series Panel Meters

To Order (Specify Model Number)   Prices Shown in Pounds

Basic Model Power & Display Inputs Control/BCD Output Analogue Output Serial Output
INF(*) ( ) ( ) ( ) ( ) ( )

Basic Model
Code Description Price
U Universal Input £499
P Process Input 422
T Thermocouple Input 460
R RTD Input 460
S Strain Input 422
W Weighing/Scale 460
PT Process Timer 460

Power & Display
Code Description Price
0 115 Vac, red LED N/C
1 230 Vac, red LED N/C
2 115 Vac, green LED N/C
3 230 Vac, green LED N/C
4 10-32 Vdc, red LED (N/A with INFPT or INFW) £85
5 10-32 Vdc, green LED (N/A with INFPT or INFW) 85

Control and BCD Outputs
Code Description Price
0 Four open collector N/C
1 Isolated parallel BCD £ 85
2 Dual 7 amp relays 55
3 Dual 7 and dual 1 A relays 130

Analogue Outputs (N/A on INFPT)
Code Description Price
0No analogue output N/C
1Analogue output £85

Serial Communications
Code Description Price
0 No serial output N/C
1 Isolated RS-232 £85
2 Isolated RS-485 85

INFINITY Series Ordering Example: INFT-5200 is a thermocouple input meter powered by 10-32 Vdc with a green display and dual 7A relays, £630.

INF7 Only

To Order (Specify Model Number)   Prices Shown in Pounds

Basic Model Power & Display Inputs Control/BCD Output Analogue Output Serial Output
INF7(*) ( ) ( ) ( ) ( ) ( )

Power & Display
Code Description Price
0 115 Vac, red LED £306
1 230 Vac, red LED 306
2 115 Vac, green LED 306
3 230 Vac, green LED 306

Inputs
Code Description Price
0 5 V CMOS, open collector N/C
1 Magnetic pickup, NPN, PNP, NAMUR £ 45
2 Isolated analogue input 150

Control and BCD Outputs
Code Description Price
0 Four open collector outputs N/C
1 BCD output, isolated, parallel £ 85
2 Dual 7 A relays 55
3 Dual 7 and dual 1 A relays 130

Analogue Outputs
Code Description Price
0No analogue output N/C
1Analogue output £85

Serial Communications
Code Description Price
0 No serial output N/C
1 Isolated RS-232 serial communications £85
2 Isolated RS-485 serial communications 85

INF7 Ordering Example: INF71202 is a 230 Vac powered meter with the Isolated analogue input board for 4-20 mA inputs and RS-485 serial communications output.

 

Accessories

Model Description Price
9SC2 9-pin RS-232 connector £23
9SC4 9-pin RS-485 connector 23
25SC2 25-pin RS-232 connector 23
25SC4 25-pin RS-485 connector 23

 